Rheem · Furnace

20 Twinning fault

Medium severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95P

What the control is telling you

Twinning was detected and then lost in the same power cycle.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115)

Likely causes

  • TWIN wire broken or disconnected
  • Controls not identical (different part numbers)
  • 24 VAC transformers out of phase
  • TWIN setting wrong on a single furnace

Test and repair steps

  1. Check the wire between the TWIN terminals of both controls and the C and W connections (802P: also W2).
  2. Confirm both IFCs have the same part number (R95P manual: UT 1194-200 board).
  3. Check transformers are in phase (out of phase makes flame LED dim); both furnaces must be on the same power phase.
  4. For a single (non-twinned) furnace make sure TWIN is set to single / nothing connected.
  5. R95P see twinning wiring diagrams Fig. 43 (1-stage) and Fig. 44 (2-stage).

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

11 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Other codes on the same units

  • 10 One-hour lockout
  • 11 Failed ignition
  • 12 Low flame sense
  • 13 Flame lost
  • 14 Unexpected flame
  • 22 Main limit open
  • 26 Line and neutral reversed
  • 33 Rollout switch (MRLC) open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.32, 40, 51; R95P: Twinning section and fault table, p.80 (PDF p.84). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.