Rheem · Furnace

33 Rollout switch (MRLC) open

Critical severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95PRGPE/RGLE

What the control is telling you

A manual-reset limit (flame roll-out switch) has opened - flame rolled out of the burner area. Must be reset by hand. RGPE/RGLE: can indicate a blocked exhaust flue; thermostat shows Call For Service.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+

Likely causes

  • Blocked flue or vent
  • Blocked or cracked heat exchanger
  • Overfiring / wrong orifice or high gas pressure
  • Combustion air problem / combustion restriction

Test and repair steps

  1. Warning: Do not jumper the roll-out switch. Find and fix the cause before resetting - fire and CO risk.
  2. Inspect vent/flue and heat exchanger for blockage.
  3. Check gas pressure and orifice size.
  4. Check combustion air supply; 802P: test with closet door closed if installed in a closet.
  5. Check the burner compartment for signs of rollout and wiring between IFC and the switch.
  6. Reset only after the cause is corrected, then watch a full heat cycle.

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Models that show this code

21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

  • 20 Twinning fault
  • 22 Main limit open
  • 23 HALC limit open (HALC LIMIT OPEN)
  • 26 Line and neutral reversed
  • 44 Low pressure switch closed (stuck)
  • 45 Low pressure switch open - inducer high speed
  • 46 Low pressure switch open - inducer low speed
  • 55 Pressure switch stuck closed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 48, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; user menus p.52; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.