Rheem · Furnace
23 HALC limit open (HALC LIMIT OPEN)
What the control is telling you
Heat Assisted Limit Control open. HALC is only on downflow/horizontal models; when it opens it often means the main blower stopped turning unexpectedly. Thermostat also shows Call For Service / CHECK FURNACE to the homeowner.
Applies to: RGPE/RGLE 2-stage 80+
Likely causes
- Blower stopped or failed (60/61/68)
- Airflow restriction
- Loose HALC wiring
Test and repair steps
- Check whether the ECM blower is running; troubleshoot blower faults first.
- Check for airflow restrictions dirty filter, dirty blower wheel, closed dampers or registers.
- Check wiring between IFC and the HALC.
- Check temperature rise is within range.
- Check the HALC resets once the blower runs; replace if open at normal temperature.
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| RGPE upflow/horizontal 05 | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
Models that show this code
10 models in RGPE/RGLE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: RGPE/RGLE: Table 16 p.49 / Table 20; user menus p.52. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.