Rheem · Furnace
14 Unexpected flame
What the control is telling you
Flame sensed when the gas valve should be closed. 802P/R95P: amber flame LED blinks rapidly; 1-hour lockout (14 and 10 alternate) that starts once flame is gone. RGPE/RGLE: thermostat also shows Call For Service / CHECK FURNACE.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Gas valve leaking through or stuck open
- Gas valve relay on IFC stuck closed
- Voltage fed to the gas valve by miswiring
- Heat call (W) not fully removed
Test and repair steps
- Warning: If flame or gas will not shut off, close the manual gas valve to the appliance BEFORE shutting off electrical power.
- Remove the heat call and confirm W to C = 0 V at the IFC.
- Check for voltage at the gas valve with no call; if present, check wiring and the IFC gas valve relay (replace IFC if stuck).
- If no voltage but flame remains, replace the gas valve.
- Do not reset until the cause is found.
Settings for these units
Clearance to combustibles (all models) · R95P
| Location | Minimum clearance |
|---|---|
| Left side | 0 in. |
| Right side | 0 in. |
| Back | 0 in. |
| Top | 1 in. |
| Front | 2 in. |
| Vent | 0 in. |
| Service (front) | 24 in. recommended |
Same values for R95PA040 through 115.
Column order read from a rotated drawing header - confirm on the furnace clearance label.
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.