Rheem · Furnace
10 One-hour lockout
What the control is telling you
Gas heat is locked out for 1 hour, then the control retries automatically. On 802P and R95P, 10 alternates with the code that caused it (11, 13, 14, 61; R95P also 59). On RGPE/RGLE the thermostat shows IGN 1 HR RTRY plus Call For Service / CHECK FURNACE. R95P manual inconsistency: its flowchart says lockout shows as '1'.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Repeated failed ignition (4 trials)
- Flame lost 5 times in one heat call
- Unexpected flame
- Dead blower - main limit open more than 150 seconds (802P, R95P)
- Unexpected voltage on the gas valve circuit that clears when the inducer stops (802P, R95P)
- R95P: water sensed again within 5 minutes of the next heat attempt in the same call
Test and repair steps
- Read the code shown with 10 (or the fault buffer) and troubleshoot that fault first.
- 802P / R95P on power-up the 3 most recent faults less than one week old flash newest to oldest.
- RGPE/RGLE on power reset the last five codes show newest first.
- Lockouts clear when the fault is fixed and power is cycled; a soft lockout can also be cleared by removing the heat call for more than 2 but less than 20 seconds.
- RGPE/RGLE shut off main power, wait 30 seconds and restore, or remove and re-establish the heat call.
- While locked out, cooling and fan calls still run but the display shows the lockout code (802P, R95P).
- If nothing is done the lockout resets itself after 1 hour.
Settings for these units
Clearance to combustibles (all models) · R95P
| Location | Minimum clearance |
|---|---|
| Left side | 0 in. |
| Right side | 0 in. |
| Back | 0 in. |
| Top | 1 in. |
| Front | 2 in. |
| Vent | 0 in. |
| Service (front) | 24 in. recommended |
Same values for R95PA040 through 115.
Column order read from a rotated drawing header - confirm on the furnace clearance label.
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes / Lockout, p.40-41; R95P: Lockout section, p.88 (PDF p.92); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.