Rheem · Furnace

11 Failed ignition

High severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95PRGPE/RGLE

What the control is telling you

No flame proven during the ignition trial. The system tries 4 times, then goes into a 1-hour lockout (10 and 11 alternate on 802P/R95P). 802P: valve opens on low fire for 8 seconds, spark up to 7 seconds, flame must prove for 1 second. R95P/RGPE: valve powered about 7 seconds per trial. RGPE/RGLE: not stored back-to-back in the fault buffer.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+

Likely causes

  • No gas, manual valve switch off, or low gas pressure
  • Spark igniter not sparking, cracked, disconnected or misplaced
  • Dirty flame sensor or poor sensor wiring
  • L1 and neutral reversed
  • Poor ground
  • Blocked orifice / gas restriction
  • R95P: pressure switch or limit opening during the trial

Test and repair steps

  1. Warning: Verify gas valve inlet and outlet (manifold) pressure with a manometer.
  2. Confirm the gas valve switch is ON and gas is supplied.
  3. Watch for spark check igniter wires, connection, cracks and placement/alignment.
  4. Clean the flame sensor rod (fine steel wool, Scotch-Brite or sandpaper) and check its wire to the IFC (RGPE/RGLE: J1 pin 1).
  5. Verify L1/neutral polarity at the IFC and junction box and check ground.
  6. Check orifices and burner alignment; confirm flame carries across all burners.
  7. R95P check 24 V at the gas valve during the trial and wiring IFC to valve; on 90+ check the aux limit and (upflow) drain pressure switch are closed.
  8. R95P if a pressure switch or limit opened during the trial, troubleshoot that circuit (57 / 22).

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Models that show this code

21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

  • 10 One-hour lockout
  • 12 Low flame sense
  • 13 Flame lost
  • 14 Unexpected flame
  • 20 Twinning fault
  • 22 Main limit open
  • 23 HALC limit open (HALC LIMIT OPEN)
  • 26 Line and neutral reversed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.