Rheem · Furnace
44 Low pressure switch closed (stuck)
What the control is telling you
Low-fire pressure switch (LPC) is closed when it should be open, before the inducer starts. The furnace will not start a heat cycle. RGPE/RGLE: thermostat shows Call For Service.
Applies to: 802P/80MDP (802PA050-150); RGPE/RGLE 2-stage 80+
Likely causes
- Pressure switch contacts welded
- Shorted or miswired switch wiring
- Water in switch or hose
Test and repair steps
- With the inducer off, check LPC contacts - must be open.
- Check switch wiring for a short.
- Check switch and hoses for water or moisture.
- Replace the switch if contacts stay closed.
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| 050 (5) | 14 in. | 0 in. | 4 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 075 (7) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 100 (10) | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 125 (12) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 150 (15) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
15 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), RGPE/RGLE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.