Midea · Heat pump

PC0L Outdoor unit low-temperature protection

Low severity Midea DLCURA ducted single-zone inverter heat pump (outdoor)

What the control is telling you

Outdoor ambient is below the unit's operating range, so it stops. Operating range: regular models heat down to -5°F (-15°C), High Heat models to -22°F (-30°C); cooling down to 5°F (regular) / -22°F (High Heat).

Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)

Likely causes

  • Outdoor temperature below operating limit
  • T4 sensor reading incorrectly

Test and repair steps

  1. Compare actual outdoor temperature with the model's operating range.
  2. If the outdoor temperature is within range, check the T4 ambient sensor.
  3. Use backup/supplemental heat (terminal W / D) while below range.

Settings for these units

Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)

SideMinimum
A - top24 in. (610 mm)
B - right side (service side)24 in. (610 mm)
C - front (air outlet)24 in. (610 mm)
D - left side4 in. (101 mm)
E - rear (air inlet)4 in. (101 mm)
Above max snow depth2 in. (50 mm)

Side letters taken from Fig. 8 drawing.

Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.

Models that show this code

12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)

DLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABK

Other codes on the same units

  • LC06 Inverter module (IPM) high temperature protection
  • PC00 Inverter module (IPM) protection
  • PC0A Condenser high temperature protection
  • PC0F PFC module protection
  • PC02 Compressor top temperature protection
  • PC06 Compressor discharge temperature protection
  • PC08 Outdoor over-current protection
  • PC10 Outdoor low AC voltage protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.