PC10 Outdoor low AC voltage protection

Medium severity Midea DLCURA ducted single-zone inverter heat pump (outdoor)

What the control is telling you

Incoming AC voltage is too low.

Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)

Likely causes

  • Supply voltage below 187 V
  • Loose connection at disconnect or terminal block
  • Undersized wire

Test and repair steps

  1. Warning: Live voltage testing - use proper PPE.
  2. Measure voltage at the outdoor terminal block with the unit running; acceptable range is 187-253 V.
  3. Tighten connections at the disconnect and terminal block.
  4. Check wire size and breaker per the electrical data (MCA/MOCP).
  5. Have the utility or electrician correct low supply voltage.

Settings for these units

Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)

SideMinimum
A - top24 in. (610 mm)
B - right side (service side)24 in. (610 mm)
C - front (air outlet)24 in. (610 mm)
D - left side4 in. (101 mm)
E - rear (air inlet)4 in. (101 mm)
Above max snow depth2 in. (50 mm)

Side letters taken from Fig. 8 drawing.

Units facing each other: 59 in. (150 cm) or more; do not blow into another unit's inlet.

Models that show this code

12 models in Midea DLCURA ducted single-zone inverter heat pump (outdoor)

DLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABK

Other codes on the same units

  • PC0L Outdoor unit low-temperature protection
  • PC02 Compressor top temperature protection
  • PC06 Compressor discharge temperature protection
  • PC08 Outdoor over-current protection
  • PC11 Outdoor DC bus high voltage protection
  • PC12 DC bus high voltage protection / 341 MCE error
  • PC30 System high pressure protection
  • PC31 System low pressure protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.