Rinnai · Tankless water heater

SS Service Soon alert (also listed as 55)

Low severity SENSEI RX/CXSENSEI

What the control is telling you

Time-based service reminder configured at installation (Parameter 03). It means the unit is due for service and the heat exchanger should be flushed.

Applies to: SENSEI Series, SENSEI RX/CX Series

Likely causes

  • Service interval set in Parameter 03 has elapsed
  • Heat exchanger due for flushing (scale risk with hard water)

Test and repair steps

  1. Flush the heat exchanger to prevent damage (owner's manual section 6.3, Flushing the Heat Exchanger).
  2. Treat hard water to prevent scale build-up and heat exchanger damage.
  3. SENSEI Reset SS by pressing the On/Off button on the temperature controller five times within five seconds.
  4. SENSEI RX/CX Reset SS by pressing and holding the "A" button until SS clears.
  5. Confirm Parameter 03 is set as intended A = not active, B = 0.5 yr, C = 1 yr, D = 2 yrs (see owner's manual section 4.12 for SENSEI, 4.13 for SENSEI RX/CX).

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

30 models in SENSEI RX/CX, SENSEI

CU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRUR160eRUR160iRUR199eRUR199iRX130iRX160iRX180iRX199iRXP160iRXP199i

Other codes on the same units

  • 66 Bypass flow servo fault
  • 70 PC board fault
  • 71 Gas solenoid valve fault (SV0–SV4 on Non-SENSEI)
  • 72 Flame rod fault
  • FF Maintenance performed (history marker)
  • LC Scale build-up in heat exchanger (LC, LC0–LC9, 00)
  • SE Cascade diagnostic display (error on secondary unit)
  • SEt Initial settings not yet confirmed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.66. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.