Rinnai · Tankless water heater

72 Flame rod fault

High severity Non-SENSEIRH180 hybridSENSEI RX/CXSENSEI

What the control is telling you

The flame rod circuit is not sensing flame properly, due to wiring, rod position, carbon build-up, low flame current, a heat exchanger leak or a board fault.

Applies to: SENSEI Series, SENSEI RX/CX Series, Non-SENSEI Series

Likely causes

  • Broken or damaged flame rod wiring
  • Flame rod not contacting the flame
  • Carbon build-up on the flame rod
  • Flame current below 1 micro amp
  • Leaking heat exchanger
  • Faulty PC board

Test and repair steps

  1. Inspect the harness from the flame rods to the PC board for broken or damaged connections.
  2. Confirm the flame rod sits in the flame when the heater fires.
  3. Remove the flame rod and look for carbon build-up; replace the rod and gasket if needed.
  4. Measure flame rod output; it must hold at least 1 micro amp.
  5. Replace the flame rod and its gasket.
  6. Check the heat exchanger for leaks and replace it if necessary.
  7. Replace the PC board.
  8. SENSEI Transfer data from the old board with the supplied cable, or program all parameters manually per PCB Replacement Instructions (100000553).
  9. SENSEI RX/CX Transfer data from the old board with the supplied cable, or program all parameters manually per PCB Replacement Instructions (100000854).

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

89 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI

C199eC199iCU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRU80eRU80iRU90eRU98e

Other codes on the same units

  • 65 Water flow control device (servo) fault
  • 66 Bypass flow servo fault
  • 70 PC board fault
  • 71 Gas solenoid valve fault (SV0–SV4 on Non-SENSEI)
  • 73 Burner thermocouple fault
  • 79 Water leakage detected
  • FE Flammable vapors detected
  • FF Maintenance performed (history marker)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.60. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.