Rinnai · Tankless water heater

57 Burner overheat bi-metal switch open

Critical severity Non-SENSEIRH180 hybrid

What the control is telling you

One of the two bi-metal switches at the back of the burner assembly has opened. The code shows whether or not the unit is running and clears only after the fault is fixed and power is cycled (hard reset).

Applies to: Non-SENSEI Series (KB Series condensing: see Technical Bulletin 107)

Likely causes

  • Loose, broken or damaged bi-metal switch wiring
  • Heater connected to the wrong gas type
  • Low/high fire manifold pressures set incorrectly
  • Improper gas conversion (pressures or DIP switches not matched)
  • Failed bi-metal sensor

Test and repair steps

  1. Inspect the harness from the burner overheat bi-metal switch to the PC board for loose, broken or damaged connections.
  2. Confirm the heater's gas type matches the supply (e.g., a natural gas unit on natural gas).
  3. Warning: Only a person qualified to service gas systems should perform the following gas checks.
  4. Check low and high fire manifold pressures using the gas pressure setting procedure for the installation's elevation.
  5. If the unit was ever converted to another gas type, confirm the conversion followed the manufacturer's instructions and that pressures and DIP switches match the new gas.
  6. Warning: Disconnect power to the heater, then replace the bi-metal sensor.
  7. After correcting the fault, hard reset by turning power off and back on.
  8. KB Series condensing units refer to Rinnai Technical Bulletin 107 for troubleshooting codes 14 and 57.

Settings for these units

RUCS/RUS unit clearances · Non-SENSEI

LocationRUCS indoor to combustiblesRUCS indoor to non-combustiblesRUS outdoor to combustiblesRUS outdoor to non-combustibles
Top6 in. (152 mm) *2 in. (51 mm) *12 in. (305 mm)2 in. (51 mm)
Back0 in.0 in.0 in.0 in.
Front6 in. (152 mm)6 in. (152 mm)--
Front (panel)--24 in. (610 mm)0 in.
Front (exhaust)--24 in. (610 mm)24 in. (610 mm)
Sides2 in. (51 mm)1/2 in. (13 mm)6 in. (152 mm)1/8 in. (3.2 mm)
Ground/bottom12 in. (305 mm)12 in. (305 mm)12 in. (305 mm)2 in. (51 mm)
Vent0 in.0 in.--

0 in. from vent components and condensate drain line.

Service clearance 24 in. in front of the heater; closet installs need 6 in. (152 mm) in front.

RUCS/RUS water quality limits · Non-SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg / L
AluminumUp to 0.2 mg / L
ChloridesUp to 250 mg / L
CopperUp to 1.0 mg / L
Dissolved CO2Up to 15.0 mg / L or PPM
IronUp to 0.3 mg / L
ManganeseUp to 0.05 mg / L
pH6.5 to 8.5
TDSUp to 500 mg / L
ZincUp to 5 mg / L

Scale build-up shows as code LC# on a controller (LC on the status monitor without one); flush the heat exchanger.

ScaleCutter parts: 103000038 (system), 103000039 (refill).

Models that show this code

59 models in Non-SENSEI, RH180 hybrid

C199eC199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRU80eRU80iRU90eRU98eRU98iRUC80iRUC90iRUC98iRUCS65iRUCS75iRUR98eRUR98iRUS65eRUS75eV53DeV53eV65eV65iV75eV75iV94XiV94eV94i

Other codes on the same units

  • 41 Freeze protection / outdoor air temperature sensor fault
  • 51 Inlet water temperature thermistor fault
  • 52 Gas valve / modulating solenoid valve (POV) signal fault
  • 54 High exhaust gas temperature
  • 58 Secondary heat exchanger bi-metal switch open
  • 61 Combustion fan motor fault
  • 63 Recirculation low flow
  • 65 Water flow control device (servo) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.50. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.