Rinnai · Tankless water heater

41 Freeze protection / outdoor air temperature sensor fault

Medium severity Non-SENSEIRH180 hybridSENSEI RX/CXSENSEI

What the control is telling you

The freeze protection (outside air) thermistor is open, shorted or disconnected. KB units will not fire; VC units and outdoor units keep running while flashing 41 alternately with the set point.

Applies to: SENSEI and Non-SENSEI Series (external/outdoor models); all SENSEI RX/CX Series models

Likely causes

  • Loose, broken or damaged sensor harness
  • Sensor unplugged, cut or shorted
  • Sensor covered by insulation instead of exposed to outside air
  • Sensor resistance out of spec
  • Temperature controller wired to the wrong terminals

Test and repair steps

  1. Inspect the sensor harness from sensor to PC board for loose, broken or damaged connections.
  2. Make sure the sensor is exposed to outside air and not buried in insulation.
  3. With a meter set for 20K ohms, measure across the sensor plug; resistance should drop when warmed and rise when cooled.
  4. Typical values 11.4–14K ohms at 59°F, 6.4–7.8K at 86°F, 3.6–4.5K at 113°F, 2.2–2.7K at 140°F, 0.6–0.8K at 221°F.
  5. Note An open sensor on outdoor units (all RX/CX units) lets the heater keep running while flashing 41; the code clears once the issue is fixed.
  6. Confirm the temperature controller is wired to the connection point shown in the Installation and Operation manual; if it is connected anywhere else, disconnect it immediately and rewire correctly.

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

89 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI

C199eC199iCU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRU80eRU80iRU90eRU98e

Other codes on the same units

  • 33 Heat exchanger thermistor fault
  • 34 Combustion air thermistor (Non-SENSEI) / Lime detecting thermistor (RX/CX)
  • 35 Tank temperature sensor fault
  • 38 Exhaust gas temperature sensor (CO sensor on RH180)
  • 51 Inlet water temperature thermistor fault
  • 52 Gas valve / modulating solenoid valve (POV) signal fault
  • 54 High exhaust gas temperature
  • 57 Burner overheat bi-metal switch open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.