Rinnai · Tankless water heater
61 Combustion fan motor fault
What the control is telling you
The combustion fan motor is not operating correctly, due to wiring, a seized or obstructed blower, open windings, incorrect supply voltage or a control board fault.
Applies to: SENSEI Series, SENSEI RX/CX Series, Non-SENSEI Series
Likely causes
- Loose, broken or damaged fan motor wiring
- Blower wheel binding or debris in the fan housing
- Check valve behind the fan stuck closed (SENSEI / SENSEI RX/CX)
- Open fan motor windings
- Incorrect fan supply voltage from the PC board
- Faulty PC board
Test and repair steps
- Warning: Turn off power and gas before servicing the fan. Never plug or unplug the motor with power applied; doing so can damage the fan motor and other parts.
- Inspect the harness from the fan motor to the PC board for loose, broken or damaged connections.
- With power and gas off, remove the fan motor and confirm the blower wheel spins freely.
- Check the fan housing for debris that could stop the wheel from turning.
- SENSEI / SENSEI RX/CX Make sure the check valve behind the fan motor is not stuck closed.
- Measure fan motor winding resistance against the Technical Data Sheet (behind the front cover) or service manual; replace the motor if windings are open.
- SENSEI RX/CX With the unit running, measure at CN7: red #1–black #2 = 7-48 VDC; white #4–black #2 = 2-14 VDC; yellow #3–black #2 = 11-13 VDC (see Electric Circuit Table/wiring diagram).
- If windings and voltage are within spec and the fan turns freely, replace the PC board.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
89 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.52. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.