Rinnai · Tankless water heater
25 Condensate pump failure or clogged drain
What the control is telling you
Triggered when the condensate float/safety switch closes because condensate has backed up, or when the accessory condensate pump stops working.
Applies to: SENSEI Series; SENSEI RX/CX Series; Non-SENSEI Series
Likely causes
- No power to the condensate pump
- External condensate pump not working
- Clogged or frozen drain line
- Loose or damaged wiring between pump/trap and PC board
- Missing air gap in drain line
- Restricted condensate trap
Test and repair steps
- Confirm the condensate pump has power.
- Check that the external (third-party) pump operates correctly.
- Make sure the drain line is not clogged or frozen.
- Inspect wiring from the pump and from the condensate trap back to the PC board for loose, damaged or broken connections.
- Confirm the drain line includes an air gap.
- Inspect the condensate trap for restrictions.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
89 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
- 18 Gas valve air/fuel adjustment limit reached
- 19 Electrical grounding / DC circuit short
- 21 PC board data transfer error
- 22 Gas valve adjustment fault
- 30 Flammable vapor sensor activated or faulty
- 31 Burner thermocouple out of range
- 32 Outlet water temperature thermistor fault
- 33 Heat exchanger thermistor fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.