18 Gas valve air/fuel adjustment limit reached
What the control is telling you
The Smart-Sense gas valve has hit its rich or lean air/fuel adjustment limit for the selected gas type, which should not happen in normal operation.
Applies to: SENSEI RX/CX Series
Likely causes
- Wrong gas being supplied to the unit
- Parameter 10 (Gas Type) set incorrectly
- Incorrect gas valve parameters entered
- Flame rod wire disconnected or damaged
Test and repair steps
- Confirm the correct gas (natural gas or propane) is being supplied.
- Check Parameter 10 (A = Natural Gas, B = Propane). It can only be changed within 20 minutes after a power reset.
- Verify or re-enter the gas valve parameters per 'Enter Gas Valve Parameters' in the Gas Valve Replacement Instructions (100000855).
- Confirm the flame rod wire is connected and undamaged.
Settings for these units
RX supply connection sizes · SENSEI RX/CX
| Connection | Size |
|---|---|
| Gas | 3/4 in. MNPT |
| Cold inlet | 3/4 in. MNPT |
| Hot outlet | 3/4 in. MNPT |
| Condensate drain | 1/2 in. MNPT |
Vent connection: 2 in. nominal PVC/CPVC/PP or 3 in./5 in. concentric.
Full specs (input, flow, weight) are only on each model's spec sheet, not in this manual.
RX water quality limits · SENSEI RX/CX
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Water damage beyond these limits is not covered by warranty.
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
- RX temperature settings available · SENSEI RX/CX
Models that show this code
10 models in SENSEI RX/CX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.