Rinnai · Tankless water heater
17 Venturi blockage
What the control is telling you
The unit has detected a blocked venturi or restricted air path; after cleaning, a manual reset sequence on the PC board is needed to return to normal operation.
Applies to: SENSEI Series; SENSEI RX/CX Series
Likely causes
- Condensate drain line not draining
- Obstruction in intake, exhaust chamber or vent termination
- Debris build-up in the venturi assembly
Test and repair steps
- Confirm the condensate drain line drains properly.
- Inspect the full vent system (intake, exhaust chamber, termination) for obstructions.
- Remove the gas valve and venturi assembly from the fan motor and inspect the venturi for debris.
- Clean the venturi assembly, reinstall it, then perform the code 17 reset on the PC board.
- SENSEI reset With controller off, press button B for 1 s repeatedly through t, F, S, E (E shows only with code 17/52 active), then hold A and B for 10 s until ECL appears.
- SENSEI RX/CX reset With controller off, press button B for 1 s repeatedly through dES, t, AdJ, F, A, E (E shows only with code 17/52 active), then hold A and B for 10 s until ECL appears.
- Once ECL is displayed the reset is complete and the water heater should resume normal operation.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
30 models in SENSEI RX/CX, SENSEI
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.28–29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.