Rinnai · Tankless water heater

31 Burner thermocouple out of range

High severity Non-SENSEIRH180 hybrid

What the control is telling you

Burner thermocouple reading is outside its allowed range: above 30 mV (possible over-firing) or below 8 mV (low gas pressure or low-Btu gas) during combustion.

Applies to: RH180 (Hybrid Tank-Tankless Non-SENSEI Series); Non-SENSEI Series

Likely causes

  • Manifold gas pressures set incorrectly for altitude
  • DIP switches set incorrectly
  • Over-firing from high manifold pressure
  • Blocked heat exchanger fins
  • Low gas pressure or low Btu gas content
  • Failed thermocouple

Test and repair steps

  1. Check low and high fire manifold pressures and set them for your altitude per the Service Manual or Technical Data Sheet inside the front cover.
  2. Confirm all PC board DIP switches are set correctly for altitude (see Technical Data Sheet).
  3. Measure thermocouple output during combustion; normal is 20–27 mV. Code 31 triggers above 30 mV or below 8 mV.
  4. Above 30 mV verify high fire manifold pressure. If within spec, remove manifold and burners and check heat exchanger fins; clean or replace the heat exchanger if clogged.
  5. Below 8 mV verify forced low fire gas pressure. If within spec, contact Rinnai Technical Support.
  6. If the fault persists, replace the thermocouple.

Settings for these units

RUCS/RUS unit clearances · Non-SENSEI

LocationRUCS indoor to combustiblesRUCS indoor to non-combustiblesRUS outdoor to combustiblesRUS outdoor to non-combustibles
Top6 in. (152 mm) *2 in. (51 mm) *12 in. (305 mm)2 in. (51 mm)
Back0 in.0 in.0 in.0 in.
Front6 in. (152 mm)6 in. (152 mm)--
Front (panel)--24 in. (610 mm)0 in.
Front (exhaust)--24 in. (610 mm)24 in. (610 mm)
Sides2 in. (51 mm)1/2 in. (13 mm)6 in. (152 mm)1/8 in. (3.2 mm)
Ground/bottom12 in. (305 mm)12 in. (305 mm)12 in. (305 mm)2 in. (51 mm)
Vent0 in.0 in.--

0 in. from vent components and condensate drain line.

Service clearance 24 in. in front of the heater; closet installs need 6 in. (152 mm) in front.

RUCS/RUS water quality limits · Non-SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg / L
AluminumUp to 0.2 mg / L
ChloridesUp to 250 mg / L
CopperUp to 1.0 mg / L
Dissolved CO2Up to 15.0 mg / L or PPM
IronUp to 0.3 mg / L
ManganeseUp to 0.05 mg / L
pH6.5 to 8.5
TDSUp to 500 mg / L
ZincUp to 5 mg / L

Scale build-up shows as code LC# on a controller (LC on the status monitor without one); flush the heat exchanger.

ScaleCutter parts: 103000038 (system), 103000039 (refill).

Models that show this code

59 models in Non-SENSEI, RH180 hybrid

C199eC199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRU80eRU80iRU90eRU98eRU98iRUC80iRUC90iRUC98iRUCS65iRUCS75iRUR98eRUR98iRUS65eRUS75eV53DeV53eV65eV65iV75eV75iV94XiV94eV94i

Other codes on the same units

  • 19 Electrical grounding / DC circuit short
  • 25 Condensate pump failure or clogged drain
  • 30 Flammable vapor sensor activated or faulty
  • 32 Outlet water temperature thermistor fault
  • 33 Heat exchanger thermistor fault
  • 34 Combustion air thermistor (Non-SENSEI) / Lime detecting thermistor (RX/CX)
  • 35 Tank temperature sensor fault
  • 38 Exhaust gas temperature sensor (CO sensor on RH180)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.