KeepRite · Furnace

4 Limit or rollout circuit open

High severity KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage Furnace

What the control is telling you

The main limit or flame rollout switch is open. The blower runs at least 4 minutes or until the switch closes. If open longer than 3 minutes the code becomes 7. The rollout switch must be reset by hand.

Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces

Likely causes

  • Dirty filter or restricted ductwork
  • Loose blower wheel
  • Gas input set too high
  • Wrong limit switch or missing limit gasket
  • Faulty switch or wiring

Test and repair steps

  1. Replace or clean the filter and check that supply/return registers are open.
  2. Check the blower wheel is tight on the shaft and turning at speed.
  3. Clock the gas meter and correct the manifold pressure if the furnace is overfired.
  4. Check the limit is the correct part and its gasket is in place.
  5. If the rollout switch tripped, find out why (combustion air, venting, burner alignment) before pressing reset.
  6. Check switch continuity and wiring.

Settings for these units

Models that show this code

16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 1+2 Blower running after power-up (normal)
  • 2 Pressure switch stuck closed (did not open)
  • 3 Pressure switch did not close or reopened
  • 5 Flame sensed with gas valve off
  • 6 Flame not proved during ignition trial
  • 6+1 Ignition lockout after 4 failed tries
  • 7 Limit circuit lockout
  • 8 Gas heating lockout - manual reset needed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.