KeepRite · Furnace

8 Gas heating lockout - manual reset needed

Critical severity KeepRite (F/G)9MXE Single-Stage FurnaceKeepRite (F/G)9MXT Two-Stage Furnace

What the control is telling you

The control has locked out gas heat and will NOT reset itself. Turn power off for 5 minutes, then retry.

Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces

Likely causes

  • Gas valve relay on the board stuck closed
  • Gas valve wire miswired or shorted

Test and repair steps

  1. Warning: this lockout points to a valve circuit fault - check carefully before restoring gas.
  2. Turn power off, wait 5 minutes, power back on.
  3. Inspect the gas valve wiring for miswiring or a short.
  4. If the code returns with good wiring, replace the furnace control.

Settings for these units

Models that show this code

16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422AG9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

Other codes on the same units

  • 5 Flame sensed with gas valve off
  • 6 Flame not proved during ignition trial
  • 6+1 Ignition lockout after 4 failed tries
  • 7 Limit circuit lockout
  • 9 High-heat pressure switch or relay did not close or reopened
  • 10 Line voltage polarity reversed
  • LED off Status LED dark - no power to the control or blown 3 A fuse
  • LED steady ON Status LED on solid - control lockout (resets after 1 hour)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.