KeepRite · Furnace
2 Pressure switch stuck closed (did not open)
What the control is telling you
At the start of a heat call the control expects the pressure switch(es) to be open before the inducer starts, and found one closed.
Applies to: KeepRite (F/G)9MXE single-stage and (F/G)9MXT two-stage 95% furnaces
Likely causes
- Pressure switch contacts welded/stuck closed
- Blocked pressure tube holding the switch closed
- Miswired switch
Test and repair steps
- Turn power off and check the pressure tubes for blockage or kinks.
- With the inducer off, check the switch contacts for continuity - they should be open.
- Replace a switch that reads closed with the inducer off.
- Check wiring at the switch matches the wiring diagram.
Settings for these units
- Filter size by casing width · KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace
Models that show this code
16 models in KeepRite (F/G)9MXE Single-Stage Furnace, KeepRite (F/G)9MXT Two-Stage Furnace
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 troubleshooting flow chart, p.24-25; KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16, p.24-25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.