06 Low recirculation flow (warning only)

Low severity Noritz NRCR

What the control is telling you

NRCR only. Warning that recirculation flow is low; the owner's guide groups 06, 061 and 062 as recirculation abnormality.

Applies to: Noritz NRCR92 / NRCR111

Likely causes

  • Clogged return line filter
  • Air in the hot/return line (dedicated mode)
  • Clogged crossover valve filter or valve installed the wrong way (crossover mode)

Test and repair steps

  1. Clean the return line filter.
  2. Dedicated mode purge air from the domestic hot and return lines.
  3. Crossover mode clean the crossover valve filter and check valve orientation.
  4. Check MM17 recirculation flow rate and MM86 recirculation mode.
  5. Contact Noritz if the warning keeps returning.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

2 models in Noritz NRCR

NRCR111DVNRCR92DV

Other codes on the same units

  • 10 Abnormal combustion (NRCR, gas supply related)
  • 11 Ignition failure (no flame detected)
  • 12 Flame loss (repeated)
  • 14 Thermal fuse failure
  • 16 Abnormally high outlet temperature
  • 20 High limit switch tripped
  • 061 Recirculation abnormality (sub-code of 06)
  • 062 Recirculation abnormality (sub-code of 06)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), NRCR Pro specific error codes, p.29; Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.