Noritz · Tankless water heater

20 High limit switch tripped

High severity Noritz EZNoritz NRCRNoritz CDVNoritz NRC/NRCP

What the control is telling you

The high limit switch on the heat exchanger opened because of overheating. Same meaning on all families.

Applies to: All Noritz residential tankless (EZ, NRCR, NCC199CDV, NRC/NRCP)

Likely causes

  • Scale deposits in the heat exchanger
  • Poor combustion
  • Bad wiring or a failed high limit switch

Test and repair steps

  1. Descale the heat exchanger and clean the inlet filter; check water hardness.
  2. Check combustion inlet gas pressure, venting, and a clean fan/venturi and burner on premix units.
  3. Turn off power and check the high limit switch wiring and connector for damage.
  4. Check the switch for continuity at room temperature; replace if open.
  5. Warning: Do not jumper the high limit switch.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

12 models in Noritz EZ, Noritz NRCR, Noritz CDV, Noritz NRC/NRCP

EZ111DVEZ71DVEZ98DVN-0841MCN-0841MC-DVN-0842MCN-0842MC-DVNCC199CDVNRC111-DVNRC111-SVNRCR111DVNRCR92DV

Other codes on the same units

  • 11 Ignition failure (no flame detected)
  • 12 Flame loss (repeated)
  • 14 Thermal fuse failure
  • 16 Abnormally high outlet temperature
  • 29 Condensate collector water level abnormal
  • 061 Recirculation abnormality (sub-code of 06)
  • 062 Recirculation abnormality (sub-code of 06)
  • 63 Recirculation abnormality (no recirculation flow)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR/CDV Level 2 Maintenance & Troubleshooting (Premix R2 V2), 16 & 20 error codes, p.14; Noritz Residential Level 2 Maintenance & Troubleshooting (NRC/NRCP and older, R2 V1), 14, 16, 20 error codes, p.8; Noritz NRCR Pro training (NRCR92/NRCR111, Printable V3), Poor water quality issues, p.32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.