Noritz · Tankless water heater

062 Recirculation abnormality (sub-code of 06)

Low severity Noritz NRCR

What the control is telling you

NRCR only. Listed with 06 in the owner's guide as recirculation abnormality.

Applies to: Noritz NRCR92 / NRCR111

Likely causes

  • Clogged return line filter
  • Clogged crossover valve filter
  • Air in the return line

Test and repair steps

  1. Clean the return line filter.
  2. Clean the crossover valve filter and check its orientation.
  3. Purge air from the hot and return lines (dedicated mode).
  4. Follow code 06 / 63 steps if it returns.

Settings for these units

Indoor clearances (required and recommended) · Noritz NRCR

LocationRequiredRecommended (service)
Top12 in. (300 mm)3 in. (76 mm) above and below exhaust
Front4 in. (100 mm)24 in. (610 mm)
Sides3 in. (76 mm)8 in. (203 mm)

Required clearances apply to both combustible and non-combustible materials.

Recommended space is for service and quick access to gas and water shut-offs.

Operation panel menu settings and defaults · Noritz EZ, Noritz NRCR

SettingOptionsDefault
Max Set Temperature (power off)100-140 F in 5 F steps; 37-48 C, 50-60 C120 F / 50 C
Recirc ON/OFFON / OFFOFF
Recirc ModeAlways OFF, Always ON, Manual Timer, Auto Learning (NRCR)Always OFF
Vacation ModeActive / InactiveInactive
Flow Meter Alarm10-60 gal (5 gal steps), 70-100 gal (10 gal steps), OFFAlarm OFF
Drain Water (power off)Start / CancelCancel
Scale Flushing (power off)Start / CancelCancel
Audible AlarmON / OFFON
Screen LockActive / Inactive (4-digit password)Inactive
Units (first 10 min after power-up, power off)[F/gal/ft] or [C/L/m][F/gal/ft]
Power Saving Dis. / BacklightON-OFF / Power Save ON-OFFON / Power Save ON
Brightness / Contrast / Touch SoundBright-Normal-Dim-Dark / -15 to +15 / ON-OFFNormal / Standard / ON

Setting 125 F (55 C) or higher needs Max Set Temperature raised first; the panel warns about scald risk.

Default Settings resets everything in Settings except Screen Lock (hold OK about 5 s).

Models that show this code

2 models in Noritz NRCR

NRCR111DVNRCR92DV

Other codes on the same units

  • 14 Thermal fuse failure
  • 16 Abnormally high outlet temperature
  • 20 High limit switch tripped
  • 061 Recirculation abnormality (sub-code of 06)
  • 63 Recirculation abnormality (no recirculation flow)
  • 65 Main water control servo abnormality
  • 66 Bypass water control servo abnormality
  • 73 Circuit board setting abnormality

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Noritz EZ/NRCR Owner's Guide (Rev. 10-25), Checking for error conditions, p.31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.