Lennox · Furnace

E160 Refrigerant leak sensor #1 wrong type

Medium severity Lennox ML180UHE

What the control is telling you

Sensor #1 is not a type approved for this application. Clears when a suitable sensor is detected; the blower then latches on for at least 5 minutes.

Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)

Likely causes

  • Non-approved or wrong replacement sensor installed on LGWP1

Test and repair steps

  1. Check the part number of sensor #1 against the Lennox approved sensor for the coil (kit 27V53 for Lennox coils).
  2. Replace with a Lennox approved sensor; with a non-Lennox coil use the coil maker's recommended sensor.
  3. Press the LGWP test button to retest.

Settings for these units

Filter sizes by cabinet width · Lennox ML180UHE

CabinetSide returnBottom return
A - 14-1/2 in.16 x 25 x 1 (1)14 x 25 x 1 (1)
B - 17-1/2 in.16 x 25 x 1 (1)16 x 25 x 1 (1)
C - 21 in.16 x 25 x 1 (1)20 x 25 x 1 (1)
D - 24-1/2 in.16 x 25 x 1 (2)24 x 25 x 1 (1)

Filters are field supplied; check monthly.

Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.

Models that show this code

12 models in Lennox ML180UHE

ML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DK

Other codes on the same units

  • E150 A2L refrigerant leak alarm
  • E151 A2L sensor fault
  • E152 Refrigerant leak sensor #2 fault
  • E154 Refrigerant leak sensor #1 communication lost / wrong DIP setting
  • E155 Refrigerant leak sensor #2 communication lost
  • E161 Refrigerant leak sensor #2 wrong type
  • E163 Furnace control board failure
  • E164 Low GWP test mode active

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.14; Optional accessories, p.3. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.