Lennox · Furnace
E155 Refrigerant leak sensor #2 communication lost
What the control is telling you
The control has lost communication with refrigerant detection sensor #2. The blower latches on for at least 5 minutes after communication returns.
Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)
Likely causes
- Damaged or unplugged sensor #2 harness or connector
- Sensor #2 damaged or plug obstructed
- LGWP2 enabled with no second sensor fitted
Test and repair steps
- Confirm whether a second sensor is required/installed; if not, set LGWP2 to Disable.
- Check the sensor #2 cable at the LGWP2 plug for proper seating, damage or moisture.
- Inspect the harness route (right side grommet) for cuts or pinches.
- Press the LGWP test button to retest the fault after repair.
Settings for these units
Filter sizes by cabinet width · Lennox ML180UHE
| Cabinet | Side return | Bottom return |
|---|---|---|
| A - 14-1/2 in. | 16 x 25 x 1 (1) | 14 x 25 x 1 (1) |
| B - 17-1/2 in. | 16 x 25 x 1 (1) | 16 x 25 x 1 (1) |
| C - 21 in. | 16 x 25 x 1 (1) | 20 x 25 x 1 (1) |
| D - 24-1/2 in. | 16 x 25 x 1 (2) | 24 x 25 x 1 (1) |
Filters are field supplied; check monthly.
Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.
Models that show this code
12 models in Lennox ML180UHE
Other codes on the same units
- E150 A2L refrigerant leak alarm
- E151 A2L sensor fault
- E152 Refrigerant leak sensor #2 fault
- E154 Refrigerant leak sensor #1 communication lost / wrong DIP setting
- E160 Refrigerant leak sensor #1 wrong type
- E161 Refrigerant leak sensor #2 wrong type
- E163 Furnace control board failure
- E164 Low GWP test mode active
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.14; Table 17, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.