46 Brown-out (low voltage)

Medium severity KeepRite *SA/*SH Single-Stage CommunicatingKeepRite *CA/*CH Two-Stage Communicating

What the control is telling you

Single-stage boards (and C4A3/CXA6 board): 24 V control voltage below 15.5 V for 4 s; runs again at 17.5 V or more. Two-stage boards: line voltage below 187 V for 4 s; runs again above 190 V.

Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Likely causes

  • Weak or overloaded 24 V transformer
  • Low utility line voltage
  • Loose power or control wiring

Test and repair steps

  1. Single-stage / C4A3-CXA6 measure 24 V at the outdoor board - it should be 18-30 V. Check transformer size and load.
  2. Two-stage measure line voltage at the contactor under load.
  3. Tighten loose connections and recheck.

Models that show this code

11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960*SH4*SH5*SH6

Other codes on the same units

  • 25 Model plug missing or invalid
  • 31 High pressure switch open
  • 32 Low pressure switch open
  • 45 Outdoor control board failure
  • 47 No 230 V at the unit
  • 53 Outdoor air temperature sensor fault
  • 55 Outdoor coil sensor fault
  • 56 Air and coil sensors disagree

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.