KeepRite · Heat pump
25 Model plug missing or invalid
What the control is telling you
The two-stage board cannot find a valid model plug and will not run.
Applies to: KeepRite *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating
Likely causes
- Model plug missing, loose or wrong
Test and repair steps
- Check the model plug is fitted and seated.
- Compare its part number and resistances with the model plug table for the unit size.
- On a replacement board, move the original plug over.
Models that show this code
8 models in KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.