31 High pressure switch open
What the control is telling you
The high-pressure switch (two-stage: or discharge temperature switch) opened. The compressor stops, the outdoor fan keeps running up to 15 minutes, then a restart is tried.
Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating
Likely causes
- Overcharge
- Outdoor fan not running
- Dirty or blocked outdoor coil (cooling)
- Low indoor airflow (heat pump in heating)
Test and repair steps
- Confirm the outdoor fan runs and the coil is clean.
- Check refrigerant charge.
- On a heat pump in heating, check indoor airflow and filter.
- Cycling 24 V skips the 15 minute wait.
Models that show this code
11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.