56 Air and coil sensors disagree

Medium severity KeepRite *SA/*SH Single-Stage CommunicatingKeepRite *CA/*CH Two-Stage Communicating

What the control is telling you

The air and coil thermistor readings do not make sense together. Cooling: air sensor more than 10°F warmer or 20°F cooler than the coil sensor. Heat pump heating: more than 35°F warmer or 10°F cooler.

Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Likely causes

  • One sensor drifting or misplaced
  • Sensor relocated from its factory spot
  • Wiring fault

Test and repair steps

  1. Ohm both sensors and compare with the chart.
  2. Check both are in their factory locations (do not move them).
  3. Check wiring; replace the faulty sensor.

Models that show this code

11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960*SH4*SH5*SH6

Other codes on the same units

  • 46 Brown-out (low voltage)
  • 47 No 230 V at the unit
  • 53 Outdoor air temperature sensor fault
  • 55 Outdoor coil sensor fault
  • 71 Low stage thermal cutout
  • 72 Compressor thermal cutout (two-stage: high stage)
  • 73 Contactor stuck closed
  • 74 No 230 V at compressor

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.