FlowMax · Combi boiler
E35 Flame detection fault (false flame)
What the control is telling you
The board is detecting a flame signal when it should not, or the flame circuit is faulty.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Ionization electrode faulty or dirty
- Ionization electrode lead faulty
- Control board faulty
Test and repair steps
- Turn off power and gas before removing the electrode.
- Inspect the ionization electrode; clean it, or replace it if damaged.
- Check the ionization lead and replace it if faulty.
- If the code remains, replace the control board.
- Warning: Gas work only by a qualified gas technician; leak-test all gas connections after any repair.
Settings for these units
Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
| Location | Service clearance (in) | To combustibles |
|---|---|---|
| X (side) | 0 | 0 in |
| Y (side) | 0 | 0 in |
| L | 16 | - |
| H | 24 | - |
| A (above) | 12 | 0 in from jacket top |
| B (below) | 12 | - |
| Front | - | 0 in |
| Rear | - | 0 in |
Wall-mount on a flat, solid vertical wall that can carry the weight.
Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.
Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
| Temperature setting | Time to 2nd/3rd degree burn (adult skin) |
|---|---|
| Over 170°F | Nearly instantaneous |
| 160°F | About 1/2 second |
| 150°F | About 1-1/2 seconds |
| 140°F | Less than 5 seconds |
| 130°F | About 30 seconds |
| 120°F or less | More than 5 minutes |
120°F lowers scald risk; children, elderly and disabled people burn faster.
Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).
Models that show this code
2 models in FlowMax condensing combi (FLOWMAX-90/120)
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.