FlowMax · Combi boiler

E14 Air pressure switch tripped

High severity FlowMax condensing combi (FLOWMAX-90/120)

What the control is telling you

Listed only in the 120 diagnostics list. The 120 troubleshooting table puts air pressure switch faults under E02 instead; checks below come from that E02 entry.

Applies to: FLOWMAX-90, FLOWMAX-120

Likely causes

  • Air pressure switch faulty
  • Intake or exhaust vent blocked
  • Air pressure switch wiring loose

Test and repair steps

  1. Inspect the intake and exhaust vent pipes and terminals for blockage and clear them.
  2. Check the vent length is within the 100 ft maximum equivalent length (each 90° short elbow = 7.5 ft, each 45° = 2.5 ft).
  3. Check the air pressure switch wiring and sensing hoses.
  4. Replace the switch if it does not close with the fan running and venting clear.

Settings for these units

Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)

LocationService clearance (in)To combustibles
X (side)00 in
Y (side)00 in
L16-
H24-
A (above)120 in from jacket top
B (below)12-
Front-0 in
Rear-0 in

Wall-mount on a flat, solid vertical wall that can carry the weight.

Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.

Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)

Temperature settingTime to 2nd/3rd degree burn (adult skin)
Over 170°FNearly instantaneous
160°FAbout 1/2 second
150°FAbout 1-1/2 seconds
140°FLess than 5 seconds
130°FAbout 30 seconds
120°F or lessMore than 5 minutes

120°F lowers scald risk; children, elderly and disabled people burn faster.

Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).

Models that show this code

2 models in FlowMax condensing combi (FLOWMAX-90/120)

FLOWMAX-120FLOWMAX-90

Other codes on the same units

  • E03 Flue gas thermostat / exhaust thermofuse tripped
  • E05 Heating (supply) sensor fault
  • E06 Domestic hot water (DHW) sensor fault
  • E12 DHW storage tank (cylinder) sensor fault
  • E16 Fan (blower) fault
  • E22 Parameter programming request
  • E35 Flame detection fault (false flame)
  • E42 Fan speed control board fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.