FlowMax · Combi boiler

E06 Domestic hot water (DHW) sensor fault

Medium severity FlowMax condensing combi (FLOWMAX-90/120)

What the control is telling you

The DHW sensor reads out of range. The 120 troubleshooting table does not list E06; checks below follow the same sensor procedure the manual gives for E05/E12.

Applies to: FLOWMAX-90, FLOWMAX-120

Likely causes

  • DHW sensor faulty
  • DHW sensor wire disconnected or wet

Test and repair steps

  1. Turn off power before working on sensor wiring.
  2. Check the DHW sensor connector and wiring for looseness, damage or moisture.
  3. Unplug and measure the sensor; the manual's other sensors are 10 kOhm at 25°C (77°F) - confirm the DHW sensor spec against the parts list.
  4. Replace the sensor if it reads open or shorted.
  5. Restart and confirm the code clears.

Settings for these units

Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)

LocationService clearance (in)To combustibles
X (side)00 in
Y (side)00 in
L16-
H24-
A (above)120 in from jacket top
B (below)12-
Front-0 in
Rear-0 in

Wall-mount on a flat, solid vertical wall that can carry the weight.

Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.

Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)

Temperature settingTime to 2nd/3rd degree burn (adult skin)
Over 170°FNearly instantaneous
160°FAbout 1/2 second
150°FAbout 1-1/2 seconds
140°FLess than 5 seconds
130°FAbout 30 seconds
120°F or lessMore than 5 minutes

120°F lowers scald risk; children, elderly and disabled people burn faster.

Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).

Models that show this code

2 models in FlowMax condensing combi (FLOWMAX-90/120)

FLOWMAX-120FLOWMAX-90

Other codes on the same units

  • E01 Ignition / ionization lockout (no flame)
  • E02 Safety (overheat) thermostat or air pressure switch tripped
  • E03 Flue gas thermostat / exhaust thermofuse tripped
  • E05 Heating (supply) sensor fault
  • E12 DHW storage tank (cylinder) sensor fault
  • E14 Air pressure switch tripped
  • E16 Fan (blower) fault
  • E22 Parameter programming request

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.