FlowMax · Combi boiler
31 Incompatible remote control
What the control is telling you
Function code shown when the connected remote control is not compatible with the circuit board.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Remote control model not compatible with the board
Test and repair steps
- Check the model of the remote control connected to the terminal board.
- Replace it with a compatible remote, or disconnect it and use the unit's own controls.
Settings for these units
Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
| Location | Service clearance (in) | To combustibles |
|---|---|---|
| X (side) | 0 | 0 in |
| Y (side) | 0 | 0 in |
| L | 16 | - |
| H | 24 | - |
| A (above) | 12 | 0 in from jacket top |
| B (below) | 12 | - |
| Front | - | 0 in |
| Rear | - | 0 in |
Wall-mount on a flat, solid vertical wall that can carry the weight.
Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.
Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
| Temperature setting | Time to 2nd/3rd degree burn (adult skin) |
|---|---|
| Over 170°F | Nearly instantaneous |
| 160°F | About 1/2 second |
| 150°F | About 1-1/2 seconds |
| 140°F | Less than 5 seconds |
| 130°F | About 30 seconds |
| 120°F or less | More than 5 minutes |
120°F lowers scald risk; children, elderly and disabled people burn faster.
Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).
Models that show this code
2 models in FlowMax condensing combi (FLOWMAX-90/120)
Other codes on the same units
- E01 Ignition / ionization lockout (no flame)
- E02 Safety (overheat) thermostat or air pressure switch tripped
- E03 Flue gas thermostat / exhaust thermofuse tripped
- E05 Heating (supply) sensor fault
- E06 Domestic hot water (DHW) sensor fault
- E12 DHW storage tank (cylinder) sensor fault
- E14 Air pressure switch tripped
- E16 Fan (blower) fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics, Function codes, p.67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.