Carrier · Furnace

25 Invalid model selection or setup error

Medium severity 59TP6A

What the control is telling you

If 25 flashes only 4 times at power-up, model plug PL4 is missing and the control is using the model stored in memory. Flashing continuously indicates a setup error.

Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)

Likely causes

  • Model plug PL4 missing and no valid model stored (common on replacement controls)
  • Thermostat call with SW1-1 ON
  • Thermostat call with SW1-6 ON
  • SW1-1 and SW1-6 both ON
  • Two different furnace models twinned
  • Wrong replacement control (needs non-modulating board, software V17 or later)

Test and repair steps

  1. Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
  2. Check that model plug PL4 is installed on the control, especially after a control replacement.
  3. Set SW1-1 and SW1-6 OFF for normal operation.
  4. If twinned, confirm both furnaces are the same model.
  5. On a replacement control, verify it is the non-modulating board with software V17 or later.
  6. Restore power and confirm the code clears.

Settings for these units

Filter sizes by casing width and filter cabinet · 59TP6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide16 x 25 x 3/4 in.16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide16 x 25 x 3/4 in.20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide16 x 25 x 3/4 in.24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

No internal filter rack in this furnace - an external filter is required.

Side-return filters can differ in size - measure the existing filter.

Minimum clearances to combustibles · 59TP6A

PositionClearance
Rear0 in. (0 mm)
Front (combustion air openings)1 in. (25 mm)
Front, required for service24 in. (610 mm) - check local code
All sides of supply plenum1 in. (25 mm) - check local code
Sides0 in. (0 mm)
Vent0 in. (0 mm)
Top of furnace1 in. (25 mm)

Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.

Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.

Models that show this code

8 models in 59TP6A

59TP6A040-1059TP6A040-1259TP6A060-1259TP6A060-1459TP6A080-1659TP6A080-2059TP6A100-2059TP6A120-22

Other codes on the same units

  • 14 Ignition lockout
  • 15 Blower motor lockout
  • 21 Gas heating lockout
  • 22 Abnormal flame-proving signal
  • 23 Pressure switch did not open
  • 24 Secondary (24 V) fuse open
  • 31 High-heat pressure switch or relay did not close or reopened
  • 32 Low-heat pressure switch did not close or reopened

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.