Carrier · Furnace

22 Abnormal flame-proving signal

Critical severity 59TP6A58SB0A/58SB1A

What the control is telling you

Flame is sensed while the gas valve is supposed to be off. The inducer keeps running (high speed) until the fault clears.

Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)

Likely causes

  • Gas valve stuck open or leaking through

Test and repair steps

  1. Warning: Flame with the valve de-energized means gas may be flowing; shut off gas at the manual valve immediately.
  2. Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
  3. Check if burners stay lit after the heat call ends.
  4. Replace the gas valve if it is stuck open or leaky.
  5. Leak-check gas connections and confirm the flame goes out at the end of the cycle.

Settings for these units

Filter sizes by casing width and filter cabinet · 59TP6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide16 x 25 x 3/4 in.16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide16 x 25 x 3/4 in.20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide16 x 25 x 3/4 in.24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

No internal filter rack in this furnace - an external filter is required.

Side-return filters can differ in size - measure the existing filter.

Minimum clearances to combustibles · 59TP6A

PositionClearance
Rear0 in. (0 mm)
Front (combustion air openings)1 in. (25 mm)
Front, required for service24 in. (610 mm) - check local code
All sides of supply plenum1 in. (25 mm) - check local code
Sides0 in. (0 mm)
Vent0 in. (0 mm)
Top of furnace1 in. (25 mm)

Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.

Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.

Models that show this code

22 models in 59TP6A, 58SB0A/58SB1A

58SB0A045E14--1258SB0A045E17--1258SB0A070E14--1258SB0A070E17--1258SB0A070E17--1658SB0A070E21--1658SB0A090E17--1458SB0A090E21--1658SB0A090E21--2058SB0A090E24--2058SB0A110E21--2058SB0A110E24--2058SB0A135E24--2058SB0A155E24--2059TP6A040-1059TP6A040-1259TP6A060-1259TP6A060-1459TP6A080-1659TP6A080-2059TP6A100-2059TP6A120-22

Other codes on the same units

  • 12 Blower on after power-up (normal)
  • 13 Limit circuit lockout
  • 14 Ignition lockout
  • 15 Blower motor lockout
  • 21 Gas heating lockout
  • 23 Pressure switch did not open
  • 24 Secondary (24 V) fuse open
  • 25 Invalid model selection or setup error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89; Sequence of Operation, p.85. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.