21.1 24 VAC on gas valve when it should be off

Critical severity 59SC6A

What the control is telling you

The control detects 24 VAC at the gas valve circuit when no gas valve output should be present.

Applies to: Carrier 59SC6A

Likely causes

  • Gas valve relay on control stuck or failed
  • Miswired or shorted gas valve circuit

Test and repair steps

  1. Warning: Shut off gas to the furnace immediately if burners stay lit with no call for heat.
  2. Remove the thermostat call and measure voltage at the gas valve terminals.
  3. Inspect gas valve wiring for shorts or miswiring.
  4. If 24 VAC remains on the valve with no call and wiring is correct, replace the furnace control.
  5. Program any new control with the Model Program Number on the rating plate (app via NFC or correct super plug).

Settings for these units

Filter sizes by casing width and filter cabinet · 59SC6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide(1) 16 x 25 x 3/4 in.(1) 20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

Side-return filters can differ in size - measure the existing filter.

Every return-air inlet needs a filter.

Minimum clearances to combustibles · 59SC6A

PositionMinimum clearance
Rear0
Front (combustion air openings in furnace and in structure)1 in. (25 mm)
Required for service24 in. (610 mm) (see note)
All sides of supply plenum1 in. (25 mm) (see note)
Sides0
Vent0
Top of furnace1 in. (25 mm)

Service and supply-plenum values are marked 'consult local building codes'.

Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.

Models that show this code

11 models in 59SC6A

59SC6A026M14--1059SC6A040M14--1059SC6A040M17--1259SC6A060M14--1259SC6A060M17--1659SC6A080M17--1659SC6A080M21--2059SC6A100M21--2059SC6A100M21--2259SC6A120M24--2259SC6A140M24--22

Other codes on the same units

  • 13.1 Limit lockout - main limit open over 3 minutes
  • 14.1 Ignition lockout after 4 tries
  • 14.2 Lockout - flame lost 3 times after 70 s of heating
  • 14.3 Lockout - 7 flame-loss events in one heat call
  • 22.1 False flame
  • 23.1 Main pressure switch stuck closed
  • 23.2 Secondary pressure switch stuck closed
  • 24.1 Fuse fault (24 V)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label Information, p.54. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.