Carrier · Furnace
24.1 Fuse fault (24 V)
What the control is telling you
The 3-amp automotive blade fuse on the control's 24 V circuit is open.
Applies to: Carrier 59SC6A
Likely causes
- Short in thermostat wiring
- Short in accessory wiring (humidifier, outdoor unit control)
- Shorted 24 V component
Test and repair steps
- Warning: Turn off power before touching the fuse.
- Confirm the 3-amp automotive blade fuse on the control is open.
- Find the short first disconnect thermostat wires and check R and each terminal to C for a short.
- Check humidifier (24 VAC HUM, 0.5 A max) and outdoor unit/accessory wiring for shorts or chafing.
- Replace with a 3-amp fuse ONLY.
- Restore power and run heat, cool and fan to confirm the fuse holds.
Settings for these units
Filter sizes by casing width and filter cabinet · 59SC6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | (1) 16 x 25 x 3/4 in. | (1) 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
Side-return filters can differ in size - measure the existing filter.
Every return-air inlet needs a filter.
Minimum clearances to combustibles · 59SC6A
| Position | Minimum clearance |
|---|---|
| Rear | 0 |
| Front (combustion air openings in furnace and in structure) | 1 in. (25 mm) |
| Required for service | 24 in. (610 mm) (see note) |
| All sides of supply plenum | 1 in. (25 mm) (see note) |
| Sides | 0 |
| Vent | 0 |
| Top of furnace | 1 in. (25 mm) |
Service and supply-plenum values are marked 'consult local building codes'.
Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.
Models that show this code
11 models in 59SC6A
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Fig. 61 p.56; Electrical Controls and Wiring p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.