23.1 Main pressure switch stuck closed

Medium severity 59SC6A

What the control is telling you

The main (collector box) pressure switch (LPS) is closed when it should be open. The control checks that both LPS and HPS are open before it starts the inducer on a heat call.

Applies to: Carrier 59SC6A

Likely causes

  • Welded/stuck pressure switch contacts
  • Jumpered or miswired pressure switch
  • Pressure tube issue causing a false signal

Test and repair steps

  1. With no inducer running, check continuity across the LPS: it must be open (it is a normally-open switch).
  2. Check for a jumper or miswiring at the switch terminals.
  3. If an LGPS accessory is not used, confirm its factory connection is intact and not miswired.
  4. Inspect the pressure tube for kinks or water.
  5. Replace the switch if it reads closed with the inducer off.
  6. Run a heat cycle and confirm the sequence starts.

Settings for these units

Filter sizes by casing width and filter cabinet · 59SC6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide(1) 16 x 25 x 3/4 in.(1) 20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

Side-return filters can differ in size - measure the existing filter.

Every return-air inlet needs a filter.

Minimum clearances to combustibles · 59SC6A

PositionMinimum clearance
Rear0
Front (combustion air openings in furnace and in structure)1 in. (25 mm)
Required for service24 in. (610 mm) (see note)
All sides of supply plenum1 in. (25 mm) (see note)
Sides0
Vent0
Top of furnace1 in. (25 mm)

Service and supply-plenum values are marked 'consult local building codes'.

Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.

Models that show this code

11 models in 59SC6A

59SC6A026M14--1059SC6A040M14--1059SC6A040M17--1259SC6A060M14--1259SC6A060M17--1659SC6A080M17--1659SC6A080M21--2059SC6A100M21--2059SC6A100M21--2259SC6A120M24--2259SC6A140M24--22

Other codes on the same units

  • 14.3 Lockout - 7 flame-loss events in one heat call
  • 21.1 24 VAC on gas valve when it should be off
  • 22.1 False flame
  • 23.2 Secondary pressure switch stuck closed
  • 24.1 Fuse fault (24 V)
  • 25.1 No program in control
  • 25.2 Corrupted program file
  • 25.3 Twinned furnaces not identical

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Fig. 61 Wiring p.56; Sequence of Operation p.68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.