NTI · Boiler troubleshooting
Stack limit lockout (Lockout 82)
What is going on
Flue temperature went past the stack limit.
Likely causes
- Dirty combustion chamber or heat exchanger
- Stack limit set wrong
- Bad stack sensor
Check in this order
- Clean the combustion chamber and heat exchanger
- Set the stack limit to 220 F (104 C) maximum, or 149 F (65 C) for PVC exhaust in Canada
- Compare sensor resistance with the thermistor chart
Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399
More boiler guides
Related
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.