NTI · Boiler troubleshooting
Blower not running
What is going on
No blower operation on a call for heat.
Likely causes
- 5-position signal connector or 3-position power connector loose
- Blown fuse A
- Failed blower
Check in this order
- Verify the 3-position power Molex and the 5-position signal Molex are seated on the blower
- Check fuse A (it also feeds the spark generator and PUMP B)
- Measure voltage across pins 1 and 2 (black and white) of the 3-position connector; with 120 VAC present, pull the 5-position signal plug and the blower should spin at high speed - replace the blower if it does not
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
More boiler guides
Related
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.