NTI · Boiler troubleshooting
Blower runs at high speed with burner off
What is going on
Blower will not idle down in standby.
Likely causes
- Blower signal cable disconnected
- No 24 VAC to the control
Check in this order
- Check the 5-position Molex on the blower and the 4-position Molex on the control
- Check the control power LED and fuse C
- Measure 24 VAC at J8 pins 1 and 2
Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399
More boiler guides
Related
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 15.0 Troubleshooting. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.