NTI · Boiler troubleshooting
Low water cutoff / ILK OFF lockout (67)
What is going on
Burner will not fire and display reads ILK OFF.
Likely causes
- Low water in boiler
- External limit open
- Condensate blockage switch open
Check in this order
- Check water level and the internal low water cutoff
- Check any external limit wired between R and LIM
- Clean the condensate trap and drain and check the vent, then clear the lockout; if still open, test the condensate switch contacts 1 and 2 for continuity
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
More boiler guides
Related
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.