E08 Low flame signal (still running)
What the control is telling you
Flame current is weak but still high enough for the furnace to run. The S8V2 flowchart treats under 0.5 microamp as the trigger. Fix it before it turns into ignition lockouts.
Applies to: Trane S8V2 (80%, 2-stage, variable speed, Link) and S8B1 / S8X1 / S8X2 (80%, 1- and 2-stage)
Likely causes
- Dirty or oxidised flame sensor
- Sensor mispositioned
- Poor ground or loose sensor wire
Test and repair steps
- Start 1st stage heat and let flame establish.
- Set a meter to DC volts across the FP pads on the IFC (1 VDC = 1 microamp); 0.75 to 3.0 is normal, readings vary with meter type.
- If under 0.5, check sensor position against the manual figure and correct it.
- Clean or replace the sensor; check its wire and the burner ground.
- If the reading is good, look for loose wiring or connections.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
- Return filter size by cabinet width · Trane S8B1, Trane S8X1, Trane S8X2
Models that show this code
37 models in Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts); Trane 18-CE14D1-1A-EN (S8B1/S8X1/S8X2 installer's guide) - section Integrated Furnace Control Display Codes, Error Codes. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.