Trane · Furnace
E13 Blower motor size / OEM ID mismatch
What the control is telling you
The blower motor horsepower does not match what the IFC is programmed for (often after a motor or board replacement).
Applies to: Trane S8V2 only
Likely causes
- Wrong replacement motor
- IFC programmed with the wrong model
Test and repair steps
- Confirm the motor HP and that it is an authorised replacement part.
- In the Link diagnostics app compare the model and serial to the nameplate.
- If they differ, select the correct model and enter the serial number in the app.
Settings for these units
Clearance to combustibles · Trane S8V2
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
24 in. front service access.
3 in. in front of the combustion air openings.
Return filter size by cabinet width · Trane S8V2
| Cabinet width | Filter |
|---|---|
| 14-1/2 in. | 1 - 14 x 25 x 1 in. |
| 17-1/2 in. | 1 - 16 x 25 x 1 in. |
| 21 in. | 1 - 20 x 25 x 1 in. |
| 24-1/2 in. | 1 - 24 x 25 x 1 in. |
Filters are field supplied and mounted outside the cabinet.
Over 1600 CFM upflow: return on both sides, one side plus bottom, or bottom only.
Models that show this code
12 models in Trane S8V2
Other codes on the same units
- E7.2 Redundant relay (HLO output) on with no call
- E08 Low flame signal (still running)
- E11 Gas valve relay / valve circuit fault
- E12 Control fuse open
- E14 Configuration file error
- E17 Blower motor communication error
- E23 Menu data not received by combustion micro (CCM)
- E24 Internal communication error between ACM and CCM
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Integrated Furnace Control Display Codes, Table 37 Error codes; Trane FNR-SVX003A-EN (S8V2 installer's guide) - section Troubleshooting (flowcharts). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.