Rheem · Furnace
Flame LED rapid blink Amber flame LED - unexpected flame
What the control is telling you
Amber flame LED blinking rapidly means flame is sensed when it should not be. See code 14.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); Rheem (-)GRC upflow and (-)GTC downflow/horizontal 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 / 1028-928 and Invensys ICC-H1MC7-01 IFC); Rheem 90RJ and 90TJ 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 or Invensys ICC-H1MC7-01 IFC, hot surface ignition)
Likely causes
- Gas valve leaking or stuck open
- IFC gas valve relay stuck / voltage at valve with no call
- Gas valve leaking through or not shutting off
- Voltage still present at the gas valve after W is off
- Faulty IFC
Test and repair steps
- Warning: If flame stays on, close the manual gas valve before cutting power.
- Confirm W to C = 0 V at the IFC.
- Check for voltage at the gas valve; check gas valve and IFC.
- See code 14.
- Warning: If gas does not shut off, close the manual gas valve to the appliance before shutting off electrical power - risk of fire or explosion.
- With the thermostat off, confirm W to C is 0 V at the IFC.
- Check for voltage at the gas valve; if voltage is present with W off, check the IFC.
- If no voltage is present and burners/flame persist, replace the gas valve.
Settings for these units
Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
| Configuration | Cabinet width | Input (MBTU/h) | Bottom filter | Side filter | Qty |
|---|---|---|---|---|---|
| Upflow | 17-1/2 in. | 45, 60, 75 | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 21 in. | 90, 105 | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 24-1/2 in. | 120 | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Downflow | 17-1/2 in. | 45, 60, 75 | 12 x 20 in. | - | 2 |
| Downflow | 21 in. | 90, 105 | 12 x 20 in. | - | 2 |
| Downflow | 24-1/2 in. | 120 | 14 x 20 in. | - | 2 |
Filters are not factory-installed; they must be field supplied.
Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.
Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
| Configuration | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|
| Upflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Downflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Horizontal | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
Same values for every cabinet size.
24 in. service clearance recommended in front of all furnaces.
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
- Clearance to combustibles (all models) · R95P
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
Models that show this code
34 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, Rheem (-)GRC/(-)GTC 90 Plus, Rheem 90RJ/90TJ 90 Plus
Other codes on the same units
- 55 Pressure switch stuck closed
- 57 Pressure switch stuck open
- 58 Water sense circuit open
- 59 Water sensed / blocked drain
- 61 Blower fault - blower not running
- 93 Internal control fault
- Flame LED off No flame sensed (troubleshooting aid)
- Flame LED slow blink Amber flame LED - marginal flame sense
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Flame Status LED, p.43, 51; R95P: Flame Status LED, p.90 (PDF p.94); Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53 IFC Troubleshooting Guide, p.54 (printed p.53). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.