Rheem · Furnace

Flame LED rapid blink Amber flame LED - unexpected flame

Critical severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95PRheem (-)GRC/(-)GTC 90 PlusRheem 90RJ/90TJ 90 Plus

What the control is telling you

Amber flame LED blinking rapidly means flame is sensed when it should not be. See code 14.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); Rheem (-)GRC upflow and (-)GTC downflow/horizontal 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 / 1028-928 and Invensys ICC-H1MC7-01 IFC); Rheem 90RJ and 90TJ 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 or Invensys ICC-H1MC7-01 IFC, hot surface ignition)

Likely causes

  • Gas valve leaking or stuck open
  • IFC gas valve relay stuck / voltage at valve with no call
  • Gas valve leaking through or not shutting off
  • Voltage still present at the gas valve after W is off
  • Faulty IFC

Test and repair steps

  1. Warning: If flame stays on, close the manual gas valve before cutting power.
  2. Confirm W to C = 0 V at the IFC.
  3. Check for voltage at the gas valve; check gas valve and IFC.
  4. See code 14.
  5. Warning: If gas does not shut off, close the manual gas valve to the appliance before shutting off electrical power - risk of fire or explosion.
  6. With the thermostat off, confirm W to C is 0 V at the IFC.
  7. Check for voltage at the gas valve; if voltage is present with W off, check the IFC.
  8. If no voltage is present and burners/flame persist, replace the gas valve.

Settings for these units

Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus

ConfigurationCabinet widthInput (MBTU/h)Bottom filterSide filterQty
Upflow17-1/2 in.45, 60, 7515-3/4 x 25 in.15-3/4 x 25 in.1
Upflow21 in.90, 10519-1/4 x 25 in.15-3/4 x 25 in.1
Upflow24-1/2 in.12022-3/4 x 25 in.15-3/4 x 25 in.1
Downflow17-1/2 in.45, 60, 7512 x 20 in.-2
Downflow21 in.90, 10512 x 20 in.-2
Downflow24-1/2 in.12014 x 20 in.-2

Filters are not factory-installed; they must be field supplied.

Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.

Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus

ConfigurationLeft sideRight sideBackTopFrontVent
Upflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Downflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Horizontal0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.

Same values for every cabinet size.

24 in. service clearance recommended in front of all furnaces.

Models that show this code

34 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, Rheem (-)GRC/(-)GTC 90 Plus, Rheem 90RJ/90TJ 90 Plus

90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSARGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS

Other codes on the same units

  • 55 Pressure switch stuck closed
  • 57 Pressure switch stuck open
  • 58 Water sense circuit open
  • 59 Water sensed / blocked drain
  • 61 Blower fault - blower not running
  • 93 Internal control fault
  • Flame LED off No flame sensed (troubleshooting aid)
  • Flame LED slow blink Amber flame LED - marginal flame sense

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Flame Status LED, p.43, 51; R95P: Flame Status LED, p.90 (PDF p.94); Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53 IFC Troubleshooting Guide, p.54 (printed p.53). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.