Rheem · Furnace
61 Blower fault - blower not running
What the control is telling you
802P/R95P: main limit open more than 150 seconds during a heat call, so the control declares a dead blower and stops gas heat (61+22 while open, 61+10 during 1-hour lockout; 4th time in one call = hard lockout, reset by cycling the heat call). RGPE/RGLE: ECM blower not running (BLWR FLT-NO RUN), Call For Service.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Blower motor failed
- Bad blower capacitor (PSC models)
- No line voltage at blower
- Broken wiring between IFC and motor
- Severe airflow restriction
- RGPE/RGLE: no 24 V to ECM control, PFC choke problem
Test and repair steps
- 802P / R95P check line voltage between HEAT and NEUTRAL on the IFC during a heat call; check the blower capacitor.
- Check wiring and continuity between IFC and blower motor.
- RGPE/RGLE check 24 V at the ECM low-voltage connector pins 1 and 4, 115 VAC to the motor, and the PFC choke and its wiring.
- Check the blower motor and wheel; replace the motor if it does not run with correct power and signals.
- Check filter and ducts for restriction.
- Lockouts clear when the fault is fixed and power is cycled; a soft lockout can also be cleared by removing the heat call for more than 2 but less than 20 seconds.
Settings for these units
Clearance to combustibles (all models) · R95P
| Location | Minimum clearance |
|---|---|
| Left side | 0 in. |
| Right side | 0 in. |
| Back | 0 in. |
| Top | 1 in. |
| Front | 2 in. |
| Vent | 0 in. |
| Service (front) | 24 in. recommended |
Same values for R95PA040 through 115.
Column order read from a rotated drawing header - confirm on the furnace clearance label.
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 51; R95P: Lockout section, p.88 (PDF p.92); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.