Rheem · Furnace
93 Internal control fault
What the control is telling you
Internal furnace control fault. 802P/R95P: hard lockout - internal fault, or voltage on the gas valve contacts (welded relay) that does not clear when the inducer cycles; cycling the heat call will not reset it. RGPE/RGLE: CONTROL FLT, Call For Service. 802P manual lists 93 in the flowchart but not the main fault table.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- IFC internal failure
- Gas valve relay welded
- Miswiring feeding voltage to the gas valve circuit
Test and repair steps
- Warning: If flame is present or gas will not shut off with no call, close the manual gas valve first.
- Cycle power and see if the fault returns.
- Check wiring, ground and connections before condemning the IFC - most failures are not the IFC.
- RGPE/RGLE when replacing the IFC, move the original memory card to J15 of the new control.
- Replace the IFC if the fault persists.
Settings for these units
Clearance to combustibles (all models) · R95P
| Location | Minimum clearance |
|---|---|
| Left side | 0 in. |
| Right side | 0 in. |
| Back | 0 in. |
| Top | 1 in. |
| Front | 2 in. |
| Vent | 0 in. |
| Service (front) | 24 in. recommended |
Same values for R95PA040 through 115.
Column order read from a rotated drawing header - confirm on the furnace clearance label.
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
21 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE
Other codes on the same units
- 61 Blower fault - blower not running
- 66 Blower overspeed (BLOWER OVRSPEED)
- 68 No blower communication (NO BLWR COMM)
- 82 Supply air sensor fault (SA SENSOR FLT)
- d1 No shared data (NO SHARED DATA)
- d4 Memory card invalid (MEM CARD INVALD)
- d5 Card/hardware conflict (CARD-HRD CNFLCT)
- d6 Blower HP conflict (BLWR HP CNFLCT)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Lockout / Diagnostics Flowchart, p.41, 51; R95P: Lockout section, p.88 (PDF p.92); RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.