Rheem · Furnace
d5 Card/hardware conflict (CARD-HRD CNFLCT)
What the control is telling you
Memory card data is for a different furnace series; network data used if valid. Standby only (level 1).
Applies to: RGPE/RGLE 2-stage 80+
Likely causes
- Memory card from another furnace series
Test and repair steps
- Check whether the original memory card is attached to the IFC or inserted in connector J15.
- If the IFC was replaced, break the original memory card off the old control and insert it in J15 of the new one.
- Warning: Never swap memory cards or controls between furnaces or from a condenser/air handler - wrong data can cut heating airflow and trip the main limit.
- If the original card is lost, order the correct replacement memory card for this model from ProStock and insert it in J15.
- Communicating systems confirm the model in the furnace user menu under Unit Info matches the rating label.
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| RGPE upflow/horizontal 05 | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
Models that show this code
10 models in RGPE/RGLE
Other codes on the same units
- 68 No blower communication (NO BLWR COMM)
- 82 Supply air sensor fault (SA SENSOR FLT)
- 93 Internal control fault
- d1 No shared data (NO SHARED DATA)
- d4 Memory card invalid (MEM CARD INVALD)
- d6 Blower HP conflict (BLWR HP CNFLCT)
- d7 Blower manufacturer conflict (BLWR MFG CNFLCT)
- d8 Old shared data (OLD SHARED DATA)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: RGPE/RGLE: Table 16 p.49 / Table 20; memory card rules p.38-39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.