Navien · Combi boiler

E012 Flame loss

High severity Navien NCB-HNavien NFC-H

What the control is telling you

The flame went out during operation after ignition. NFC-H manual lists the reset type as: Manual reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Clogged air intake filter
  • Poor ground on the power supply
  • Low or fluctuating inlet gas pressure
  • Vent or intake restriction
  • Dirty flame detector electrode

Test and repair steps

  1. Clean the air intake filter (top left inside the cabinet; rinse, let it dry fully, reinstall).
  2. Make sure the electrical cord/outlet is properly grounded.
  3. Check inlet gas pressure at full fire against the rated range on the rating plate.
  4. Inspect the exhaust and intake piping and terminations for blockage.
  5. Clean the flame detector electrode; check Service Status Info > Flame Loss count.
  6. Reset from the front panel by pressing the Back button, then confirm the code clears.
  7. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Minimum installation clearances (indoor) · Navien NCB-H

SideMinimum
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)

Indoor wall-hung only; ambient must stay above 32°F (0°C).

Do not install on carpet; leave room for service.

Water quality limits (DHW and system fill) · Navien NCB-H

ContaminantMax allowed
Total hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5 to 8.5
Sulfate250 mg/l (DHW table); 205 mg/l (fill table)
Total dissolved solids500 mg/l
Zinc5 mg/l
Chlorine (fill water)4 mg/l

Scale damage from poor water is not covered by warranty.

Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.

Models that show this code

7 models in Navien NCB-H, Navien NFC-H

NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150HNFC-250/175HNFC-250/200H

Other codes on the same units

  • E001 Heat exchanger overheat
  • E003 Ignition failure
  • E004 False flame detected
  • E016 Heat exchanger overheat (overheating of heat exchanger)
  • E030 Exhaust overheat (abnormal exhaust temperature)
  • E031 Burner overheat
  • E046 Heat exchanger thermistor / overheat sensor fault
  • E047 Exhaust thermistor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.